SPLIT TYPE ROOM AIR CONDITIONER
INSTALLATION MANUAL
MODEL: AMS09 9000 BTU and 14.5 SEER
AMS12 12000 BTU and 13.5 SEER
WARNING
CAUTION
This symbol refers to hazard or unsafe practices which can
result in severe personal injury or death
This symbol refers to hazards or unsafe practices which can
result in severe personal injury or death and the potential for
product or property damage.
Electrical Hazard Symbols
ELECTRICAL
SAFETY / ALERT
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - INSTALLATION MANUAL

SPLIT TYPE ROOM AIR CONDITIONERINSTALLATION MANUALMODEL: AMS09 9000 BTU and 14.5 SEER AMS12 12000 BTU and 13.5 SEERWARNINGCAUTIONThis

Seite 2 - CONTENTS

i) Drainage Run the drain hose downward. Do not install the drain hose as illus-trated below.Do not form a riseDo not put the hose end into watera)

Seite 3 - IMPORTANT!

CAUTIONPerform the wiring with sufficient capacity. Installation legally requires a short circuit isolator to be attached to prevent electrical shock.

Seite 4 - SPECIAL PRECAUTIONS

CONDENSOR INSTALLATION (OUTDOOR)Install the outdoor unit on a rigid base to prevent increasing noise level and vibration. Determine the air outlet di

Seite 5 - When Servicing

CONDENSOR INSTALLATION (OUTDOOR)3) Refrigerant Piping Connectioni) Flaringii) Tightening ConnectionCut a pipe with a pipe cutterInsert a flare nut int

Seite 6 - (Split Wall-Mounted Type)

AIR PURGE AND TEST OPERATION1) Air PurgeChoose Purge method from the table.Connective Pipe Length Air Purging MethodAdditional amount of refrigerant t

Seite 7 - INSTALLATION PRECAUTIONS

AIR PURGE AND TEST OPERATIONWhen Using The Vacuum Pump (For method using a manifold valve, refer to this operation manual.)Completely tighten

Seite 8

15AIR PURGE AND TEST OPERATION2. Gas Leak CheckMake sure no gas comes out from the connections with a leak detector or soap water. CAUTIONA: Lo pack

Seite 9 - (<12000Btu/h model)

CONTENTSImportant Special PrecautionsInstallation Manual Installation PrecautionsEVAPORATOR (INDOOR) UNIT INSTALLATION 1) Mounting and Installation

Seite 10 - Evaporator (Indoor) Unit

IMPORTANT!Please Read Before Starting This air conditioning system meets strict safety and operating standards. As the installer or service person, i

Seite 11 - 5) Connecting Cables

SPECIAL PRECAUTIONS When WiringELECTRICAL SHOCK CAN CAUSE SEVERE PERSONAL INJURY OR DEATH. ONLY A QUALIFIED, EXPERIENCED ELECTRICIAN SHOULD ATTEMPT

Seite 12 - 2) Drain Elbow Installation

SPECIAL PRECAUTIONS When Connecting Refrigerant Tubing• Keep all tubing runs as short as possible.• Use the flare method for connecting tubing.• Ap

Seite 13 - 4) Wiring Connection

Part #Name of part Qty1 Installation Plate 12 Mounting Screw ST3.9 x 25-C-H83 Clip Anchor 84Refrigerant PipeLiquid SideO 1/4”Gas Side <12000 Btu/hO

Seite 14 - AIR PURGE AND TEST OPERATION

Selecting the Location for the Indoor and Outdoor Units:The following should be reviewed prior to selecting the location for your instal-lation.Evapor

Seite 15

CAUTIONConnect the (evaporator) indoor unit rst then the outdoor unit and bend and arrange the pipe carefully.Ensure there is no slack in the drain h

Seite 16

EVAPORATOR INSTALLATION (INDOOR)The Installation Plate would look like one of the following (Depending on the models):Installation plate and its dime